Dissolved Air Flotation Troubleshooting:
DAF dissolved air flotation should be regularly checked and maintained, once the machine is in abnormal, troubleshooting should be arranged to remove the faults in time.
1.
Fault: No Air-saturated Water
Fault Appearance:
Water Recirculation Pump Works Properly
Pressure from the 2 Pressure Gage of Recirculated Water and Compressed Air are Both > 3.5 kg
No Pressure Difference Between the 2 Pressure Gage of Recirculated Water and Compressed Air
Reason:
Air-saturated Water Releasers are Blocked
Valves of Air-saturated Water Releasers are Closed
Solution:
Clean Air-saturated Water Releasers
Check and Open the Valves of Air-saturated Water Releasers
2.
Fault: No Air-saturated Water
Fault Appearance:
Pressure from the 2 Pressure Gage of Recirculated Water and Compressed Air are Both > 3.5 kg
Pressure Difference Between the 2 Pressure Gage of Recirculated Water and Compressed Air is 0.6kg
Air Compressor Keep Running, Never Stop
Reason:
Compressed Air Feed is Not Enough
Solution:
Check the Inlet and Outlet Air Valves of Air Compressor
Check the Piston Ring of Air Compressor
Check and Repair the Leakage of Compressed Air Pipe
3.
Fault: Air-saturated Water Flow is Small
Fault Appearance:
Pressure from the 2 Pressure Gage of Recirculated Water and Compressed Air are Both > 3.5 kg
Pressure Difference Between the 2 Pressure Gage of Recirculated Water and Compressed Air is <0.3 kg
Water Recirculation Pump Works Properly
Reason:
Air-saturated Water Releasers are Blocked
Solution:
Clean Air-saturated Water Releasers
4.
Fault: Air-saturated Water Flow is Small
Fault Appearance:
Pressure from the 2 Pressure Gage of Recirculated Water and Compressed Air are Both <3.0 kg
Pressure Difference Between the 2 Pressure Gage of Recirculated Water and Compressed Air is 0.6kg
Water Recirculation Pump Works Properly
The Valve after Water Recirculation Pump is fully Opened
Reason:
Water Inlet of Water Recirculation Pump is Blocked
Impeller of Water Recirculation Pump is Blocked
Solution:
Clean the Water Inlet and Impeller of Water Recirculation Pump
5.
Fault: Air-saturated Water Flow is Normal in the Beginning, but No Air-saturated Water any more After Half an Hour.
Fault Appearance:
Pressure from the 2 Pressure Gage of Recirculated Water and Compressed Air are Both > 3.5 kg
Water Recirculation Pump Works Properly
Air Compressor can be Turned On/Off Normally in Manual Mode, but It can't Work in Auto Mode
Reason:
Air Compressor Control System is in Fault
Solution:
Check and Confirm Switch of Manual/Auto is in Right Position
Check Whether the Automatic Control Circuit Fall Off
6.
Fault: Water Recirculation Pump Stops Automatically After Start-up
Fault Appearance:
Water Recirculation Pump Stops Automatically after Working a Peroid of Time
Turn on Water Recirculation Pump Again, but AC Contactor Doesn't Work
Reason:
The Setting of Protection Current of Thermorelay is Improper
Solution:
Adjust Protection Current of Thermorelay
Press the Reset Button of Thermorelay
7.
Fault: After Being Unused for a Long Period of Time, DAF Machine Stops Immediately After Startup
Fault Appearance:
Press the Start Button, Dissolved Air Flotation Can Start
DAF Machine Stops Immediately Once Releasing the Start Button
Reason:
The Self-protection Wire Falls Off
Contact Resistance of Contactor is Too Large
Solution:
Connect the Self-protection Wire
Remove the Contact Resistance in Contactor of Self-protection.
For the daily maintenance of DAF Dissolved Air Flotation, please click to read: Dissolved Air Flotation Maintenance.