Dissolved Air Flotation Sizing and Calculation:
1.
Contacting Zone of Dissolved Air Flotation:
1.1
Surface Area Ac:
Ac=(Q+Qr)/(3600*Vc)
Ac: Surface Area of Contacting Zone, in m2
Q: Designed Capacity for Dissolved Air Flotation, in m3/h
Qr: Quantity/Volume of Air-saturated Water, in m3/h
Vc: Average Water Flow Velocity, generally, 10-20mm/s
1.2
Length L:
L=Ac/Bc
L: Length of Contacting Zone, in m
Bc: Width of Contacting Zone, in m
1.3
Water Depth above Weir H2:
H2=Bc
H2: Water Depth above Weir, in m
1.4
Contacting Time Tc:
Tc=(H1-H2)/Vc
Tc: Contacting Time of Contacting Zone, Tc>60s
H1: Water Depth of Air Flotation Separation Zone, generally, 1.8-2.2m
2.
Air Flotation Separation Zone:
2.1
Surface Area As:
Ac=(Q+Qr)/(3600*Vs)
As: Surface Area of Separation Zone, in m2
Vs: Average Water Down-flow Velocity, generally, 1-1.5mm/s
2.2
Length Ls:
Ls=As/Bs
Ls: Length of Separation Zone, in m
Bs: Width of Separation Zone, in m
2.3
Water Depth of Dissolved Air Flotation H:
H=Vs*t
H: Water Depth of Dissolved Air Flotation, in m
t: HRT (hydraulic retention time) of Separation Zone, generally, 10-20 minutes
2.4
Volume of Dissolved Air Flotation W:
W=(Ac+As)*H
W: Volume of Dissolved Air Flotation, in m3
2.5
Verification of Total HRT T:
T=60*W/(Q+Qr)
T: Total HRT, in minute
3.
Air Saturator/Air Dissolving Tank:
Air Saturator Diameter D:
D=[4*Qr/(π*I)]^(1/2)
D: Air Saturator Diameter, in m
I: Hydraulic Load, generally 80-150m3/(m2·h)
To the design and calculation of Dissolved Air Flotation, please click to read: Dissolved Air Flotation Design Calculation.
Contact: Eng. Dover
Mobile: +86 17561675721
Whatsapp: +86 17561675721
QQ: 1049235017
Wechat: 1049235017
Email: dover@cnwwtp.com
Addr: Beiling, Machang Vil.